2008.12.17: Resolution to Power Outage
It has been found, with the help of vendor engineers and different monitoring devices, that the root cause of the problem was the local power company, TECO. The problem is that we are not being supplied with the 480V of power from our two feeds. Instead, we are being provided a fluctuating source of power, which is not unheard of, but to the degree of over 60V in variance. This has caused our UPS systems to kick on continually to cover what it sees as a brown out. This has burned up batteries in several strings that are tied to both primary and redundant UPS systems. We have replaced the bad batteries, and now are fully aware of the actual cause for our continued plight. We have also engaged TECO to have them work to rectify their issues so that this will not be a recurring issue. Please direct all additional questions to support@sagonet.com, and we will answer them to the best we can. We thank you for your patience and understanding while we work to get this resolved.
Sincerely,
Sago Networks Engineering Team